What is the cause of AdsWarning 1861 after going into run mode in TwinCAT?


After trying to start the run mode, I get a fatal error on the target system :

Init7\IO: Set State TComObj PREOP OP >> AdsWarning: 1861 (0x745, ADS ERROR: timeout elapsed)

Anyone of you know how to fix it?


Solution

  • Is your target system running Windows 10? Has it recently been updated (Windows Update) to version 1803? If so, the problem is because TwinCAT is not compatible with the 1803-version of W10. Beckhoff did release an updated TwinCAT version 3.1.4022.20, but removed it as it caused other problems. They will release a new version in the coming days.